C-TEC ActiV Conventional 'C Class' Base VAD c/w 96dB(A) Sounder
- Approvals/certifications: Certified to EN54-3 & 23 by the LPCB & VdS
- Protocol/compatibility: Compatible with C-TEC's CFP, FP, MFP and EP203 conventional fire alarm panels and virtually all other makes (testing on third-party panels is recommended before use)
- Application/operation: Designed to be ceiling mounted – either stand-alone with a red or white cap or as part of a stacked Sounder/VAD/Detector Base combination
- VAD category & coverage: C-3-8.5 (151m3 cylindrical coverage)
- Flash rate & colour: 0.5Hz; 1Hz or OFF / White
- Supply/operating voltage: 18 to 30V DC
- Nominal SPL (Sound Pressure Level): 96dB(A)
- Alarm current: At 30Vdc: 12.2mA (0.5Hz) or 19.5mA (1Hz); At 18Vdc: 14.5mA (0.5Hz) or 25mA (1Hz)
- Product dimensions (mm): 122 x 46 (not including optional detector and base)
- IP Rating: IP21C (Type A)
- Weight: 170g
- Operating conditions/temperature: -10 to 55ºC
- Notes: For compliance to EN54-3 & EN54-23, the BF431QCP Quick Connect Plate must be used with the base device
In Stock
Product Details
- Third-party certified to EN54-3 (Sounders) and EN54-23 (VADs)
- Provides ‘C-3-8.5’ light distribution (min 0.4 lux over a 3 x 8.5m cylindrical area)
- Impressive 96dB(A) sound output @ 1m
- Includes 31 selectable primary tones and an optional secondary tone
- Two volume levels (high and low)
- Three selectable VAD flash rates (0.5Hz, 1Hz, OFF)
- Alarm Current at 30Vdc = 12.2mA (0.5Hz) or 19.5mA (1Hz)
- Alarm Current at 18Vdc = 14.5mA (0.5Hz) or 25mA (1Hz)
- Supplied with a BF431QCP quick connect plate and detector spur wires
- IP21C rated
Manufacturer | C-Tec |
---|